Configure Your Mecer / Axpert Inverter

Axpert King VMIII Inverter

The Halo Energy range of batteries are fully compatible with Axpert Inverters.

The following Installation Guide will assist you with correct battery and inverter settings you should use.

For further detailed information ensure you read the supplied manual of the battery and inverter regarding the setup and installation processes.

Halo Battery Specifications

Halo Battery Specifications
BatteryNominal Voltage (VDC)Discharge / Low Voltage Cutoff (VDC)Float Voltage (VDC)Bulk / Absorb (VDC)Recommended Max Charge (A)Recommended Max Discharge (A)
WM5484455.356.3100100

Using your Halo battery without a BMS connection

Configure your Mecer / Axpert inverter to work with the Halo battery by using the settings below

Mecer / Axpert 3kW No BMS
ParameterValueSetting NameMenu No.
Inverter Battery TypeUSE-5
MAX Charge current80 A-2
Bulk / Equilise Charge Voltage56 VCv26
Float Charge Voltage54.6 VFLv27
Low Cutoff voltage44 VCOv29

To configure your inverter, reference your inverter manual to navigate to the Menu No. selection screens on the inverter display and set the parameters as in the table above.

FAQs

How do you setup multiple batteries?

See table above and check your product manual for a more detailed explanation. You will have to set dip switch settings per battery to give them a unique address. You also have to connect the included RJ45 battery link cables into the “Battery Link” port of each battery. Ensure your master battery dip switch 1 is on, 2,3,4 is OFF. Only the master battery CAN Bus will be enabled. You can then connect the into the CAN port of the master battery for communications to work.

 

Do I have to use the communication battery link cables if I don’t want to monitor or have communications?

Yes